This article mainly discusses the common leakage phenomenon of FRP storage tanks and analyzes its causes. Eventually, we hope to find out the repair methods.
Bottom plate leakage
In general, the visual manifestation of bottom plate leakage is the corrosion phenomenon on the ground. At this time, we should first check the outside of the tank to find the leakage point and consider whether the damage of the tank is caused by the bump during the lifting process; secondly, we should consider whether the leakage is caused by the air holes inside the bottom plate due to the unqualified manufacturing process.
Solution: Open a manhole side window of about one person's shoulder width (diameter φ400) on the side of the tank, enter the tank to find the leak point, and reinforce the leak point and the entire bottom of the tank, the inner wall of the tank bottom upward within 1 meter of the all-around cladding for repair. After completion, fill with water and test for 48 hours without leakage to solve.
Flange Leakage
Flange leakage is generally caused mostly by defects in the production of the flange, as shown in Figure 3, the flange was found to be leaking drop by drop to the lower exterior.
Solution: The leaking flange will be cut and replaced, bearing in mind that when replacing the internal and external flange body and tank are required to wrap, and internal wrapping is completed to leave the tank inside the mouth to avoid blocking the flow of liquid.
Side window manhole bolt drip
If the tank comes with a side manhole, after finding the side manhole bolt dripping, you need to consider two problems: first, whether the bolt is not tightened or the gasket is damaged; second, whether the manhole flange has cracks.
Solution: Replace the gasket for the tightened bolt. If the problem is not found to be solved, remove the blind plate and find that the flange is cracked, the flange should be cut down and re-wrapped, and replaced.
In order to prevent the phenomenon of leakage, should do a good job of daily maintenance.
Maintenance of FRP storage tank
1. To prevent the work apparatus from hitting the tank wall. The use of ladders, metal parts equals the contact part of the tank wall to add soft pads to protect the inner wall from being scratched and bruised.
2. Enter the FRP acid and alkali tank maintenance, should first close all feed valves, empty and clean the tank. After testing to confirm that there is no toxic gas in the tank, no lack of oxygen to enter the tank. Enter the tank should wear soft-soled shoes, strap on the safety belt, and the other end of the safety belt tied to the top of the tank. Pay attention to the ventilation inside the tank. Into the tank operation, there must be personnel outside the tank under supervision.
3. Outdoor use of glass fiber reinforced plastic storage tanks will be used for many years due to aging of the outer surface layer, resulting in resin layer peeling or fiber exposure. It is recommended that every two or three years the outer surface of the tank should be painted or resin to prevent aging and extend service life.
4. FRP tank maintenance can not be loaded at will on the top of the tank but is also not allowed to apply external force on the receiver.
5. FRP tanks outside climbing ladders, cages, guardrails before climbing should be carefully checked whether safe and reliable, there is an abnormal situation is strictly prohibited to climb the use.